Specifications
Escala Tower PL & S, E, T System Hardware
Chapter 8: Reference Information 6/8
9es3s1c8.doc
Rev 5.9
02/12/03
3. Temperature, Relative Humidity, and Maximum Wet Bulb Requirements
Temperature Relative Humidity (non-condensing) Max Wet BulbSystem Unit or Device
Operating Non-Operating Operating Non-Operating Operating Non-Operating
Escala S 16°C to 32°C - 8% to 80% - - -
Escala E 10°C to 38°C
(50 F to 100 F)
5°C to 50°C
(41°F to 122°F)
20% to 80% 5% to 95% 24°C 28°C
Escala T 10°C to 38°C
(50 F to 100 F)
5°C to 50°C
(41°F to 122°F)
20% to 80% 5% to 95% 24°C 28°C
Escala PL220T 10°C to 40°C
(50°F to 104°F)
10°C to 52°C
(50°F to 126°F)
8% to 80% 8% to 80% 27°C
(80 F)
27°C
(80 F)
Escala PL240T 10°C to 43°C
(50°F to 109°F)
10°C to 52°C
(50°F to 126°F)
8% to 80% 8% to 80% 27°C
(80 F)
27°C
(80 F)
Escala PL400T 10°C to 38°C
(50 F to 100 F)
10°C to 43°C
(50 F to 110 F)
8% to 80% 8% to 80% 23°C
(73 F)
-
Escala PL420T 5°C to 35°C
(41 F to 95 F)
-8% to 80% - 27°C
(80 F)
-
Escala T610 10°C to 38°C
(50 F to 100 F)
10°C to 43°C
(50 F to 110 F)
8% to 80% 8% to 80% 23°C
(73 F)
27°C
(80 F)
Escala PL600T 10°C to 38°C
(50 F to 100 F)
10°C to 43°C
(50 F to 110 F)
8% to 80% 8% to 80% 23°C
(73 F)
-
Temperature Relative Humidity (non-condensing) Max Wet BulbSystem Unit or Device
Operating Non-Operating Operating Non-Operating Operating Non-Operating
Disk Expansion Cabinet (Escala E & T) 10°C to 38°C -40°C to 60°C 20% to 80% 5% to 95% 24°C 28°C
Disk Expansion Cabinet (Escala S) 10°C to 50°C -55°C to 85°C 20% to 80% 5% to 95% - -
StorageTek External 9 tracks - - 90% 95% 28°C 28°C
DLT4000 Tape Drive 10°C to 40°C 10°C to 40°C 20% to 80% 10% to 90% - -
DLT8000E - Tabletop 10°C to 40°C -40°C to 66°C 20% to 80% 5% to 95% 25°C (77°F) 46°C (114.8°F)
DAS1300/2900/3200/3500 10°C to 38°C -40°C to 65°C 20% to 80% 10% to 90% 23°C (73°F) 27°C (80°F)
DAS5700/5300/4500 (10 and 30 slots) Deskside
DAE5000 (10 and 30 slots) Deskside
10°C to 40°C -40°C to 65°C 20% to 80% 10% to 90% 23°C (73°F) 27°C (80°F)
8mm Cartridge Tape Library 5°C to 35°C -40°C to 60°C 20% to 80% - - -
Note:
If any tape drive is installed, the minimum relative humidity of a system unit is 20%. If a CD-ROM Drive is installed, the minimum relative humidity of a
system unit is 10%.