Specifications

VFDG7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
95
The start is controlled by RUN key, the stop command is controlled by STOP/RESET key,
inching and forward and reverse command are selected and controlled by multifunction
QUICK/JOGkey.Intherunningstate,ifpressRUNandSTOP/RESETkeyatthesametime,it
wouldcausethefrequencyinverterto
stopfreely.
1: Terminal start-stop (“REMOT” light is flash)
Perform run command control through multifunction input terminals forward, reverse,
forwardinching,reverseinchingandsoon.
2: Communication start-stop (“REMOT” light is on)
The run command is controlled by the communication mode of upper computer, when
selectingthisitem,theextensioncardSCEXTIOofourcompanymustbeselected.
F0.13 Terminal control running mode Default: 0
Setting scope: 04
This parameter defines 5 different modes to control the running of frequency inverter
throughouterterminals.
0:Twowirecontrol1
Thismodeisthegeneralusedtwowirecontrol.Itisusedtocontroltheforwardandreverse
run of the motor through forward function terminal and reverse function terminal.
The
settingofmultifunctionterminalisasfollow:
Terminal Setting Description
Sx 01 Forward running
Sy 02 Reverse running
The control mode is as the following figure6-2.
K1 K2 Running
command
0 0 Stop