Specifications

VFDG7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
93
Set the highest output frequency of the frequency inverter. It is the basis of frequency
settingandtheaccelerationanddecelerationspeed.
F0.06 Running frequency upper limit
Default:
50.00Hz
Setting scopeF0.07F0.05
Upperlimitvalueoffrequencyinverteroutputfrequency.Thisvalueshouldbelessthanor
equaltothemaximumoutputfrequency.
F0.07
Running frequency lowe
r
limit
Default: 0.00Hz
Setting scope0.00F0.06
Frequencyinverteroutputfrequencylowerlimitingvalue.
Relation among the three ones: maximum output frequency>=upper limiting
frequency>=lowerlimitingfrequency.
F0.08
Keyboard digital frequency
setting
Default: 50.00Hz
Setting scope0.00F0.06
When the frequency source is 0(keyboard digital setting), the function code value is
regardedastheinitialvalueoffrequencyinverterdigitalpresetfrequency.
F0.09
Running direction
setting
Default: 0
Setting scope02
0:Forwardrunning
Whenthefrequencyinverterispowered,itrunsaccordingtotheactualdirection.
1:Reverserunning
Changingthisfunction codecanchange themotor’s rotation withoutanyother parameter
changed,theeffectissametomodifyanytwolinesofthemotor’slines(U,V,W)tochange
themotor’srotation.
Note:afterparameterinitialization,themotor’srotationwillreturnto theoriginalstate.
Please caution in case the motor’s rotation is forbidden changing after the system
debugging.
F0.05
Maximum output
frequency
Default : 50.00Hz
Setting scope F0.06(Min. 5.00Hz)
600.00Hz