Chapter6FunctionalParameterDetailVFDG7SeriesFrequencyInverterOperationManual
92
company,it need to set the F8 groupparameterand refer to the communicationprotocol
explanationofChapter7.
7: PLC program running setting
The frequency inverter runs by the simple PLC program, it needs to set the F6 group
parameter.
8: HDI high-speed pulse setting
The frequency is set through the highspeed pulse input terminal, it is supported by the
expansioncardSCEXT1IOOFourcompany,itneedstosettheF4.21~F4.24parameter.
F0.02
Auxiliary frequency source
standard selection when
overlay
Default0 Setting scope01
F0.03
Auxiliary frequency scope
overlay
Default100.0% Setting scope0.0150.0%
AuxiliaryFrequencySourceStandardSelectionwhenoverlay
0:Relativetomaximumfrequency
1:Relativetomainfrequencysource
MainandAuxiliaryFrequencyCombinationModeSetting:
0:Onlymainfrequencysetting
1:Onlyauxiliaryfrequencysetting
2:QUICK/JOGorterminalswitchingselection
3:Mainfrequency+auxiliaryfrequency(thedirectionisdecided
bythemainfrequency)
4:Mainfrequency‐auxiliaryfrequency(thedirectionisdecidedbythemainfrequency)
5:Themaximumofboth(thedirectionisdecidedbythemainfrequency)
6:Theminimumofboth(thedirectionisdecidedbythemainfrequency)
F0.04
Main and auxiliary frequency
combination mode
Default: 0
Setting scope 0
6