VFDG7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
91
Chapter 6 Functional Parameter Detail
6.1 F0 Basic Function Group
F0.00 Selection of the main frequency source
Default3 Setting scope08
F0.01
Selection of the auxiliary frequency
source
Default0 Setting scope08
Select the frequency instruction input channel of the frequency inverter
0: Keyboard digital frequency setting
ItcouldbesetviaF0.08orandkeysonthepanel.
1: Analog V1 Setting
V1isthe0~10Vvoltageinput,itneedtosettheparameterF4.11~F4.15.
2: Analog V2 Setting
V2isthe0~10Vvoltageinputor4~20mAcurrentinput,whichcouldbeselectedthroughthe
jumperJP2,itneedtosettheparameterF4.16~F4.20.
Notes:whenselectingthe4~20mAinputthroughthejumperJP2,thecorrespondingvoltage
oftheinputcurrent20mAis10V.
3: Keyboard Potentiometer Setting
4: Multi-segment speed running setting
Selectingthesegmentspeedbythecombinationofmultifunctioninputterminal,toensure
the running frequency by the F4 group multifunction input terminal segment speed
selectionandthetargetsettingofF6.00~F6.15.
5: PID Control Setting
Select the process PID control output as running frequency. It is generally used in the
spot industrial art close loop control, such as constant voltage close loop control, constant
tension close loop control, it need to set the F7 group parameter.
6: Remote communication setting
The frequency instruction is set by the upper computer communication mode, through
MODBUScommunicationprotocol,itissupportedbytheexpansioncardSCEXT1IOofour