Specifications
Chapter1SafetyandNotesVFD‐G7SeriesFrequencyInverterOperationManual
5
500Vinsulation testerto measuretheinsulating resistance.It shouldnotbe lessthan
5MΩ.
Motor thermal protection
Iftheratingsofthedrivenmotor arenotincompliancewiththedrive,especially,the
drive rated power more than motor rated power, be sure to adjust the protective
thresholdortoinstallthermalrelaybeforethemotortoensurethemotorisproperly
protected.
Operate above power frequency
Thisdrivecanprovide0Hz~600Hzoutputfrequency.Iftheuserneedtorunthemotor
aboveratedfrequency,pleaseconsidertheaffordabilityofmechanicaldevices.
The mechanical device resonance
Thedrive system mayencounter mechanicalresonancewith theload whenoperating
withincertainbandofoutputfrequency.Skipfrequencieshavebeensettoavoidit.
Motor heat and noise
TheoutputvoltageisinPWMwavewithsomeharmonics.Therefore,temperaturerise,
noiseandvibrationofmotorarehigherthan50Hz.
Varistors or capacitors used to improve the power factor
Don't connectany varistor or capacitor to the output terminals of the drive, because
the drive's output voltage waveform is PWM, otherwise tripping or damaging of
components may occur; in addition, don't install circuit breaker or contactor at the
outputsideofthedrive.
Circuit breakers connected to the input/output of the drive
Ifcontactorisconnectedbetweentheinputpowersupplyandthemotor,Pleasedon’t
use contactor to control drive start‐stop. If it must be done, interval time should not
less than one‐hour. If frequently charging and discharging, the life of the internal
capacitance of the drive will be reduced.
If circuit breaker or contactor needs to be
connectedbetweenoutput sideof thedriveand the motor,besuretooperatethese
circuitbreakers orcontactor whenthedrivehas nooutput,to avoid damagingof the
drive.
Using outside the range of rated voltage
The drive is unsuitable to be used out of the specified range of operation voltage;