Specifications

Chapter 5 Function Parameter Simple List VFDG7 Series Frequency Inverter Operation Manual
83
Function
Code
Name
Setting Scope and
Introduction
Factory
Defaults
Modify Page
protection
0: Disabled
1: Enabled
Fb.02
Motor overload
protection point
20.0 120.0%(motor
rated current)
100.0% 149
Fb.03
Bus-wire over
voltage at stall
110150% 130% 150
Fb.04
Auto current
limiting threshold
100200% 170% 150
Fb.05
Frequency
decrease rate in
current limiting
0.0050.00Hz/s
0.00
Hz/s
150
Fb.06 Auto reset times 03 0 151
Fb.07
Fault automatic
reset interval time
set
0.1100.0s 1.0s 151
Fb.08
Type of third latest
fault
E000:No fault
E001:IGBT shorted
protection
0 151
Fb.09 Type of latest fault 0 151