Specifications
VFD‐G7SeriesFrequencyInverterOperationManualChapter5FunctionParameterSimpleList
56
Function
Code
Name
Setting Scope and
Introduction
Factory
Defaults
Modify Page
F2.03
VF point 1
frequency F1
0.1~F2.05 20.0% √ 112
F2.04
VF point 1 voltage
V1
0.1~F2.06 20.0% √ 112
F2.05
VF point 2
frequency F2
F2.03~F2.07 50.0% √ 112
F2.06
VF point 2 voltage
V2
F2.04~F2.08 50.0% √ 112
F2.07
VF point 3
frequency F3
F2.05 ~ 100.0% ( rated
frequency of motor)
70.0% √ 112
F2.08
VF point 3 voltage
V3
F2.06 ~ 100.0% ( rated
voltage of motor)
70.0% √ 112
F2.09
Custom V/F
percentage
50.0~100.0% 100.0% √ 113
F2.10
V/F Slip
compensation gain
0.0~200.0% 0.0% √ 113
F2.11
Suppress
oscillation enabled
0: Enabled
1: Disabled
1 √ 113
F2.12
Suppress
oscillation
low-frequency
threshold
0~500 5 √ 113
F2.13
Suppress
oscillation
high-frequency
0~500 100 √ 114