Specifications
Chapter 5 Function Parameter Simple List VFD‐G7 Series Frequency Inverter Operation Manual
49
Function
Code
Name
Setting Scope and
Introduction
Factory
Defaults
Modify Page
4: Main frequency -
auxiliary frequency ( the
direction is decided by
main frequency)
5:The maximum of both
( the direction is decided
by main frequency)
6:The minimum of both
(the direction is decided
by main frequency)
F0.05
Maximum output
frequency
F0.06(minmum5.00Hz) ~
600.00Hz
50.00 Hz × 95
F0.06
Running frequency
upper limit
F0.07~F0.05 50.00 Hz √ 95
F0.07
Running frequency
lower limit
0.00~F0.06 0.00 Hz √ 95
F0.08
Keypad digital
frequency setting
0.00~F0.05 50.00 Hz √ 95
F0.09
Running direction
setting
0: Forward running
1: Reverse running
2: Reverse forbidden
0 × 95
F0.10
Acceleration time
0
0.1~3600.0s
Type
confirm
√ 96
F0.11
Deceleration time
0
0.1~3600.0s
Type
confirm
√ 96
F0.12
Operation channel 0: Keyboard start-stop
0 × 96