Specifications
VFD‐G7SeriesFrequencyInverterOperationManualChapter3MechanicalandElectricalInstallation
36
The main control circuit terminals 
Type 
Terminal 
Symbol 
Terminal Name  Function 
Digital 
input 
S1-COM 
Multi-function 
digital input
terminal 1 
1. Opto-coupler isolation 
2. Input resistance: 3.3 KΩ 
3. Input voltage range: 9V~30V 
4. Programmable multi-function input 
S2-COM 
Multi-function 
digital input
terminal 2 
S3-COM 
Multi-function 
digital input
terminal 3 
S4-COM 
Multi-function 
digital input
terminal 4 
S5-COM 
Multi-function 
digital input
terminal 5 
S6-COM 
Multi-function 
digital input
terminal 6 
Analog 
output 
FM1-GND Analog  output  1 
Output voltage or current could be selecte
d
by the JP9 jumper of the control board. 
Output voltage range: DC 0V~10V 
Output current range: DC 0~20mA 
Digital 
output 
SP1-24V  Digital output 1 
Open collector output 
Output voltage range: DC 0V~24V 
  SP2-24V  Digital output 2  Max output current is 50mA. 