VFD‐G7SeriesFrequencyInverterOperationManualChapter3MechanicalandElectricalInstallation
34
connectedpiecebetweenPand(+),thenconnectthereactortothetwoterminals.
E. FrequencyInverterOutputSideU.V.W:
Thecapacitorsorsurgeabsorberscannotbeconnectedtotheoutputsideofthedrive.
Otherwisecausethefrequencyinvertertotripfrequentlyorevenbedamaged.
Because motor cable is too long, the impact of distributed capacitance produces
electricalresonance,which
ledtothedamageofthemotorinsulation,thedrivetriping
foragreaterleakagecurrent.Whenthecablesfromthedrivetomotorarelongerthan
100m,aACinputreactorshouldbeused.
F. EarthTerminal
The terminal must be properly earthed, ground resistance must be less than 0.1Ω.
Otherwise,leadtoequipmentabnormaloperationordamaged.
☞Notice:It is prohibited to share the earth terminal E and the power zero line
terminalN.