VFDG7SeriesFrequencyInverterOperationManualChapter3MechanicalandElectricalInstallation
34
connectedpiecebetweenPand(+),thenconnectthereactortothetwoterminals.
E. FrequencyInverterOutputSideU.V.W:
Thecapacitorsorsurgeabsorberscannotbeconnectedtotheoutputsideofthedrive.
Otherwisecausethefrequencyinvertertotripfrequentlyorevenbedamaged.
Because motor cable is too long, the impact of distributed capacitance produces
electricalresonance,which
ledtothedamageofthemotorinsulation,thedrivetriping
foragreaterleakagecurrent.Whenthecablesfromthedrivetomotorarelongerthan
100m,aACinputreactorshouldbeused.
F. EarthTerminal
The terminal must be properly earthed, ground resistance must be less than 0.1Ω.
Otherwise,leadtoequipmentabnormaloperationordamaged.
NoticeIt is prohibited to share the earth terminal E and the power zero line
terminalN.
3.2.5 Control Circuit and Wiring
1) VFDG7maincontrolcircuitterminalsdrawing
V1 S1 S2 S3 S4 S5 S6 COM
V2 10V GND FM1 SP1 SP2
PW
24V
2) Functionofthecontrolterminals
Table33VFDG7Frequencyinvertercontrolterminalintroduction
The main control circuit terminals
Type
Terminal
Symbol
Terminal Name Function
TA1 TB1 TC1