Specifications
VFD‐G7SeriesFrequencyInverterOperationManualChapter3MechanicalandElectricalInstallation
30
Name 
Install 
Location 
Function 
AC Output 
Reactor 
Between the 
output side 
of the 
frequency 
inverter and 
motor. Near 
the drive 
The output side of the frequency inverter 
generally contains more the high-order harmonics. 
When the distance between the frequency inverter 
and the motor is fart,  there is large distributed 
capacitance in the line, the high-order harmonics 
may produce resonance in loop, bring two 
influences: 
1) Destroy motor insulation performance, might 
damage the motor for a long time. 
2) Have caused a greater leakage current and the 
frequency inverter will trip frequently. 
Generally, when the cables from the frequency 
inverter to motor are longer than 100m, an output 
AC line reactor should be used. 
3.2.3 Method Of Connecting Wire 