Criteria:Checkifthereiscrackonfanvanesandotherparts.Whentheinverterisswitched
on,checkifthereisanyabnormalvibration.
2.FilteringElectrolyticcapacitors
Possible cause of damages: the quality of input power is bad, the ambient temperature is
high,frequentloadingjumpandagingof
electrolyte.
Criteria: Check if there is any leakage of liquids. Check if the safety valve protrudes.
Measurementofstaticcapacitanceandinsulationresistance.
2.8.4 Storage
Afterbuyingthe inverter,whenstore fortemporarily andlongterm,the following notesis
important:
1)Asfaraspossiblestoreintotheoriginalpackaging.
2)Longtermstoragewillcausethedeteriorationofelectrolyticcapacitors.Therefore,the
invertermustbepoweredwithin2years,andtheconductiontimeis
atleastfor5hours.
Theinputvoltagemustbeboostedgraduallytotheratedvaluebythevoltageregulator.
2.8.5 Warranty Instructions
Ourcompanywouldoffertheaftersalesif thefollowingconditionsoccurtothefrequency
inverter:
1)Freewarrantyisonlyconfinedtothefrequencyinverteritself;
2) Under normal use condition, if there is any faults or damages, our company will take
the responsibility of 12 months defects liability
period for under the normal operation
conditions(fromthemanufacturingdeliverydayon,andsubjecttothemachinebarcode).
After12months,reasonablemaintenancewillbecharged;
3). Even within 12 months, maintenance fee would be charged under the following
conditions:
Damages incurred to the inverter due to incorrect operation,
which are not in
compliancewith“UserManual”;
Damagesincurredtotheinverterduetofire,flood,abnormalvoltageandsoon;