Specifications
 Chapter2SpecificationsandSelectionVFD‐G7SeriesFrequencyInverterOperationManual
21
4)Whetherthecoolingfanofthedriveisworkingproperly.
5)WhethertheVFDisoverheating
Dailycleaning:
1)Reservethedriveinacleanstate.
2)Effectivelyremovethedustonthesurfaceoftheinvertertopreventdustenteringthe
insideoftheinverter,especiallythemetaldust.
3)Effectively
cleartheoilfromthecoolingfan.
2.8.2 Routine Checking 
Check regularly the place which is difficult to check when the drive is running, routine
checkingitems: 
1)Checktheairduct,andregularlyclean.
2)Checkwhetherthescrewsareloose.
3)Checkwhetherthedriveiscorroded.
4)Checkwhethertheterminalshavearctraces.
5)Checkwhetherthe
maincircuitisinsulation.
☞Notes:WhenusingaDC500VMega‐Ohm‐Metertotestinsulatingresistance,pleasemake
sure the mian circuit and the frequency inverter is disconnected. please don't use the
insulation resistance meterto test the insulation of the control circuit.High voltage test is
unnecessary(ithas
alreadybeenconductedbeforedelivery).
2.8.3 Replacing of Quick-wearing Parts 
The quick‐wearing parts of the frequency inverter mainly includes cooling fan and
electrolytic capacitors for filters. Their lifetime depends largely on their application
environmentandmaintenancecondition.Normally,lifetimeis:
Components  Life 
Fan 2~3 years 
Electrolyte capacitor  4~5 years 
Theusercandecidethereplaceagelimitaccordingtotherunningtime.
1.Coolingfan
Possiblecauseofdamages:wearofthebearing,agingofthefanvanes.