Specifications
 Chapter2SpecificationsandSelectionVFD‐G7SeriesFrequencyInverterOperationManual
19
1.5~2.2 SC-BR300-W300 1  300  ≥200 
3.7~5.5 SC-BR100-W500 1  500  ≥75 
7.5~11 SC-BR70-W1000 1  1000  ≥50 
15~18.5 
SC-BR50-W2000
SC-BR50-W2000 
1 2000 ≥40 
SC-CBU30T
4 
1 
22~30 2 4000 ≥20 
37~55 3 6000 ≥15 
SC-CBU55T
4 
1 
75~93 5 10000 ≥10 
SC-CBU93T
4 
1 
110~132 7 14000 ≥6 
SC-CBU200
T4 
1 
160~200 10 20000 ≥4.5 1 
220~250 13 26000 ≥3.5 
SC-CBU200
T4 
2 
280~315 17 34000 ≥2.5 
350~400 20 40000 ≥2 
2.7 Selection of DC Reactor 
SVF‐G7 Series frequency inverter, G37/P45KW~G400/P450KW all use external DC reactor,
(DCreactorusage:powergridharmonic suppression,toimprovetheinputpowerfactorof
the inverter.) Users could select the DC reactor based on actual situation. Users need to
remove the short circuit copper bars between the main circuit terminals
 (+) and P when
installation,thentheDCreactorcouldbeconnectedbetweenthe(+)andP,thereisnopole
between the reactor terminals and the inverter terminals (+), P. After installing the DC
reactor,theshortcircuitcopperbarsbetween(+)andPshortcircuitisnolonger
used.
Table2‐5SelectionofVFD‐G7VFDExternalDCreactor
VFD POWER 
(KW) 
DC Reacto
r
Configuration 
Recommended 
DC Reacto
r
TYPE 
Reactor 
Rated 
Current(A) 
N
otice 