Specifications
VFD‐G7 Series Frequency Inverter Operation ManualChapter 8 Troubleshooting
171
The drive can not charge, 
CHARGE is OFF. 
Seek service 
The MCCB trips 
after power-on 
Between the inputs of the supply 
have earth or shorted. 
Troubleshoot the issue 
Rectifier breakdown,power line 
and motor line connect wrongly 
Seek service 
The motor is 
standstill after 
the drive running 
The 3-phase outputs among U, V, 
and W are unbalance. 
Check if damaged or 
obstructed 
Set the parameters 
correctly according to 
the nameplate 
Don’t have output voltage  Seek service 
The drive 
display is 
normal, after 
power-on, the 
MCCB of the 
power trips after 
operating 
Between the phases of output 
module have shorted 
Seek service 
Between the motor’s lines have 
shorted or grounded 
Troubleshoot the issue 
The distance between the motor 
and drive is far, Occasionally trips 
Install output reactor 