VFD‐G7 Series Frequency Inverter Operation ManualChapter 8 Troubleshooting
167
Chapter 8 Troubleshooting 
Table8‐1listedthepossiblefaultsofVFD‐G7,andthefaultcodeindicaterangeisfromE001
andE004~E025.Onceafaultoccurs,youmaycheckitagainstthetableandrecorddetailed
phenomenabeforeseekingservicefromyoursupplier.
8.1 Faults and actions 
Table8‐1Faultsandactions
Fault 
code 
Fault 
categories 
Possible reasons of fault  Actions 
E001 
IGBT 
module’s 
shorted 
Too short Acc time  Prolong the Acc time 
Inside IGBT is damaged  Seek service 
Interference causes the 
malfunction 
Check peripheral equipment 
whether has strong interference 
Grounded is not good  Seeking service 
E004 
Over-current 
during 
acceleration 
Too short Acc time  Prolong the Acc time 
Low AC supply voltage  Check the input power supply 
Drive power is too small  Select a high power drive 
E005 
Over-current 
during 
deceleration 
Too short Dec time  Prolong the Dec time 
Low AC supply voltage  Use suitable dynamic braking kit 
Drive power is too small  Select a high power drive 
E006 
Over-current in 
constant speed 
operation 
Sudden change of load or 
abnormal 
Check the load or reduce the 
Sudden change of load 
Low AC supply voltage  Check the AC input power supply 
Drive power is too small  Select a high power drive 
E007 
Over-voltage 
during 
acceleration 
Abnormal input voltage  Check the input power supply 
The rotating motor 
re-starts after the drive 
stops instantly. 
Avoid re-start after the drive 
stops instantly 