Specifications
Chapter7CommunicationProtocolVFD‐G7SeriesFrequencyInverterOperationManual
164
Slave 
address 
Functi
on 
code 
Parameter 
address 
high byte 
Parameter 
address 
low byte 
Data 
high 
byte 
Dat
a 
low 
byte 
CRC 
Parity bit 
high byte 
CRC 
Parity bit 
high byte 
01 06 00  0B  01 2C CB  45 
7.3.5 Abnormal Responding Function Code 
(1)Abnormalrespondingform
Forthenormalresponse,thefrequencyinverterfeedbacktouppermachine,according
totheform4.3.1and4.3.2.
For the abnormal response, the frequency inverter return to the abnormal response
formasfollows;
Slave 
address 
Function code +80H Abnormal 
code 
CRC Parity bit 
high byte 
CRC Parity 
bit high byte 
(2)Themeaningofabnormalcode:
Modbus abnormal code 
Code  Name  Meaning 
01H Illegal function 
The received function code from PC is not allowed 
operation;the slave device handles the requirement in 
the wrong state 
02H 
Illegal data 
address 
The required address of the PC is not allowed; 
especially, register address and the number of bytes 
transmitted combination is invalid. 
03H 
Illegal data 
value 
There are not allowed value in the receiving data field. 
Note: It is never meaning that there is a value 
exceeded the application’s expectation in the data 
items submitted to store. 
06H 
The slave device 
is busy 
The drive is busy(E2PROM is storing) 