Specifications
VFD‐G7 Series Frequency Inverter Operation ManualChapter 7 Communication Protocol
163
corresponding 16 system data is 012CH, and store this setting when power‐off. Dec time
F0.11respondstheaddressof16systemisF00BH.
Andtheuppermachinesendsthedatatofrequencyinverterasfollows;
Slave
addre
ss
Function
code
Parameter
address
high byte
Parameter
address
low byte
Data
high
byte
Data
low
byte
CRC
Parity
bit high
byte
CRC
Parity bit
high byte
01 06 F0 0B 01 2C CB 45
Andthefrequencyinverterfeedbacktotheuppermachineasfollows;
Slave
address
Function
code
Parameter
address
high byte
Parameter
address low
byte
Data
high
byte
Data
low
byte
CRC
Parity
bit high
byte
CRC
Parity
bit high
byte
01 06 F0 0B 01 2C CB 45
Example2:
Thedectimeoffrequencyinverterchangesto30.0sthroughuppermachine,corresponding
16 system data is 012CH, and not store this setting when power‐off. Dec time F0.11
respondstheaddressof16systemis000BH.
Andtheuppermachinesendsthedatatofrequencyinverterasfollows;
Slave
addres
s
Functi
on
code
Parameter
address
high byte
Parameter
address
low byte
Data
high
byte
Data
low
byte
CRC Parity
bit high
byte
CRC
Parity bit
high byte
01 06 00 0B 01 2C CB 45
Andthefrequencyinverterfeedbacktotheuppermachineasfollows;