Specifications
VFD‐G7 Series Frequency Inverter Operation ManualChapter 7 Communication Protocol
163
corresponding 16 system data is 012CH, and store this setting when power‐off. Dec time
F0.11respondstheaddressof16systemisF00BH.
Andtheuppermachinesendsthedatatofrequencyinverterasfollows;
Slave 
addre
ss 
Function 
code 
Parameter 
address 
high byte 
Parameter 
address 
low byte 
Data 
high 
byte 
Data 
low 
byte 
CRC 
Parity 
bit high 
byte 
CRC 
Parity bit 
high byte 
01 06  F0  0B  01 2C CB  45 
Andthefrequencyinverterfeedbacktotheuppermachineasfollows;
Slave 
address 
Function 
code 
Parameter 
address 
high byte 
Parameter 
address low 
byte 
Data 
high 
byte 
Data 
low 
byte 
CRC 
Parity 
bit high 
byte 
CRC 
Parity 
bit high 
byte 
01 06  F0  0B  01 2C CB 45 
Example2:
Thedectimeoffrequencyinverterchangesto30.0sthroughuppermachine,corresponding
16 system data is 012CH, and not store this setting when power‐off. Dec time F0.11
respondstheaddressof16systemis000BH.
Andtheuppermachinesendsthedatatofrequencyinverterasfollows;
Slave 
addres
s 
Functi
on 
code 
Parameter 
address 
high byte 
Parameter 
address 
low byte 
Data 
high 
byte 
Data 
low 
byte 
CRC Parity 
bit high 
byte 
CRC 
Parity bit 
high byte 
01 06  00  0B  01 2C CB  45 
Andthefrequencyinverterfeedbacktotheuppermachineasfollows;










