Specifications

Chapter7CommunicationProtocolVFDG7SeriesFrequencyInverterOperationManual
162
Function Address Data and meaning
Upper-limit
frequency
setting value
2004H
0.0% 100.0% when setting 100.0% the
upper-limit frequency is equal to the max output
frequency.
Function
parameter
Function
code 16
system is
FX.YZ
High
addressFX
Low
address
YZ
Corresponding function code setting
Notice ThelifeoftheEEPROMwillbeshortenedifEEPROMisfrequentlystored.Sothe
users should reduce the times of storing EE PROM. And some parameter under
communicationmodeisnoneedtostore,andjustneedtochangethevalueinRAM.When
writingthe
RAMvalueofparameter,youcouldjustchangetheregisterhighaddressfromF
toOisok.IfwritingtheRAMofF1.11,theregisteraddressis010B.Buttheexpressmethod
ofregisteraddresscouldnotusetoreadthefrequencyinverterfunctionparameter.
2Frameincommunication
Theframethatslavemachinesendtofrequencyinverter
Slave
address
Function
code
Parameter
address high
byte
Parameter
address low
byte
Data
high
byte
Data
low
byte
Parity
bit high
byte
Parity
bit
low
byte
Frequency inverter corresponds the frame content of upper machine: frequency
inverterreturnthedataissamewithuppermachine.
3Forexample
Example1
The dec time of frequency inverter should change to 30.0s through upper machine,