Specifications
VFD‐G7 Series Frequency Inverter Operation ManualChapter 7 Communication Protocol
161
byte byte byte byte byte byte
01 03 04 13 88 15 18 70 07
7.3.4 Write operation function code
Function code Realized function: change the frequency inverters’ control command,
frequencyinstruct,functionparameter.Justmodifyasinglefrequencyinverter’sparameter
oncetime.
06:Standsforthefunctioncodeofwritingvariable
(1)Theaddressdistributionofwritingparameter
Function Address Data and meaning
Communication
control
command
1000H
0001H: Run forward
0002H: Run reverse
0003H:Jog forward
0004H: Jog reverse
0005H: Stop
0006H:Coast to stop(Emergency Stop)
0007H: Fault reset
0008H: Jog to stop
Address of
communication
setting
frequency
2000H
0.00% ~ 100.00% , when setting 10000
(corresponding 16 system:2710H),the given
frequency value is the largest frequency.
PID setting
address
2001H 0.0%~100.0%
PID feedback
address
2002H 0.0%~100.0%
Torques setting
value
2003H 0.0%~100.0%