Specifications
Chapter7CommunicationProtocolVFD‐G7SeriesFrequencyInverterOperationManual
160
Theframethatslavemachinesendtofrequencyinverter:
Slave 
address 
Function 
code 
Parameter 
address 
high byte 
Parameter 
address 
low byte 
Read 
number 
high 
byte 
Read 
number 
low 
byte 
Parity 
bit high 
byte 
Parity 
bit low 
byte 
Theframethatfrequencyinvertercorrespondingtheuppermachine:
Slave 
address 
Function 
code 
Read 
byte 
quantity 
The 
first 
data 
high 
byte 
The 
first 
data 
low 
byte 
;;; The 
n 
data 
high 
byte 
The 
n 
data 
low 
byte 
Parity 
bit 
high 
byte 
Parity 
bit 
low 
byte 
(3)Forexample
Theuppermachineread twodatafromthefrequencyinverter, andthe twodataissetting
frequency and DC bus voltage,the address is 3001H, 3002H, andthe upper machine
shouldsendthedatatofrequencyinverterasfollows;
Slave 
address 
Function 
code 
Parameter 
address 
high byte 
Parameter 
address 
low byte 
Read 
number 
high 
byte 
Read 
number 
low byte 
CRC 
Parity 
bit 
high 
byte 
CRC 
Parity bit 
high byte 
01 03 30 01 00 02 9A CB 
The setting frequency of frequency inverter is 50.00Hz (corresponding 16 system data is
1388H). Bus voltage is 5400v (corresponding 16 system data is 1518H).The frequency
inverterfeedbackstothedatatouppermachine:n=2isthenumberofvariablequantity.
Slave 
address 
Function 
code 
Read 
number 
of byte
(2*n)
The 
first 
data 
high 
The 
first 
data 
low 
The 
second 
data 
high 
The 
second 
data 
low 
CRC 
Parity 
bit 
high 
CRC 
Parity 
bit 
high 