Specifications
VFD‐G7 Series Frequency Inverter Operation ManualChapter 7 Communication Protocol
157
fault information, function code,could read 6 continuous address frequency inverter
parameteroncetime.
(1)Readableparameteraddressscatter:
Function Address Data and meaning
Operation
status
1001H
0001H:running forward
0002H:running reverse
0003H:standby status
0004H:fault status
Monitoring
parameters
3000H Operating frequency 0.01HZ
3001H Setting frequency 0.01HZ
3002H Bus voltage 0.1V
3003H Output voltage 0.1V
3004H Output current 0.1A
3005H Rotating speed 1RPM
3006H Output power 0.1%
3007H Output torque 0.1%
3008H Reference PID 0.1%
3009H Feedback PID 0.1%
300AH Terminal input state
300BH Terminal output state
300CH Analog V1 value 0.1V
300DH Analog V2 value 0.1V
300EH Reserve