Specifications
Chapter7CommunicationProtocolVFD‐G7SeriesFrequencyInverterOperationManual
156
Chapter 7 Communication Protocol
VFD‐G7 series VFD communicatewith PC,PLCetcuppermachines, andtheyneed the
support of standard expansion cards SC‐EXT1‐IO. And the cards supply RS485
communication interface. Between the upper user machine and frequency inverter
communicatethrough the international standardModBus communication, and the upper
user machine as
host machine, and the frequency inverter as slave machine. The
communication content could be finished as follows: send operating command to
frequency inverter, setting operating frequency, changing function code parameters,
reading frequencyinverter operation situation, monitoring parameters, fault information,
functioncodeetc.
7.1 Communication Allocation
SetbaudrateandparitybitthroughF8.01.
7.2 Protocol Form
Figure7‐1MODBUSprotocolform
7.3 Protocol Form Instruction
7.3.1 Data type
Allthedataispresentedby16system.
7.3.2 Salve machine address
TheaddressoffrequencyinvertershouldbesetthroughF8.00,0isbroadcastaddress,slave
addresscouldbesetto1~247.
7.3.3 Read function code
Functioncode03:presentreadingthevariantthefunctioncode.
Realized function:readingfrequency inverteroperation situation, monitoring parameters,