Figure620Illustrationofcurrentlimitationprotectionfunction
Fb.06 Fault automatic reset times
Default: 0
Setting scope: 03
Fb.07
Fault automatic reset spacing interval
setting
Default:1.0s
Setting scope 0.1
100.0s
Fault automatic reset times: When the frequency inverter select fault automatic reset, it
couldbeusedtosetthetimesofautomaticreset.Ifthecontinuousresettimesexceedthis
value,thefrequencyinverterwouldbefaultandstandby,manualinterventionisneeded.
Fault automatic reset spacing interval setting: the time interval between fault happening
andautomaticresetaction.
Fb.08 The first two times fault type
Default: 0
Setting scope025
Fb.09 The last fault type
Default: 0
Setting scope025
Fb.10 Present fault type
Default: 0
Setting scope025
Recording the latest three times fault type of the frequency inverter: 0 indicates no fault,
1~25 represents 25 different fault. The detail is shown in fault check and elimination of