Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
146
0:Invalid
1:Valid
During deceleration,the motor’s decelerate rate may be lower than that of drive’s output
frequencydue totheloadinertia. At this time,the motor willfeed the energy backto the
drive, resulting in the busbar voltage rising. Enabled over‐voltage stall protection could
preventthe
busbarvoltagerisingeffectively.
Decade:Quick current limitation action selection
0:Valid
1:Invalid
Whenquickcurrentlimitationisvalid,andtheoutputcurrentoffrequencyinverterexceeds
thecurrentlimitationlevel,thefrequencyinverter controltheoutputcurrentoffrequency
inverterwithin currentlimitationlevel throughwave current limitationmode, but it would
influencetheloadcapacityofthefrequency
inverter.
Hundred:Input phase lacking protection
0:Invalid
1:Valid
Input phase lacking protection: select whether protect the input phase lacking
situation.
Kbit:Output phase lacking protection
0:Invalid
1:Valid
Outputphaselackingprotection:selectwhetherprotecttheoutputphaselackingsituation.
Fb.01
Protection function
selection 2
Default: 0001H
Setting scope:0000H~0111H
Singledigit:Overloadprotectionselection
0:Unprotected. Without motor overload protection characteristics (use carefully), the