Specifications

VFDG7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
145
Traverse operating amplitude: the traverse operating frequency is limited by the
upper/lowerlimitoffrequency.
Thetraverseoperatingamplitudecorrespondstothecentralfrequency:
AW=centralfreq.×FA.08
Jitter frequency=AW×FA.09, which is the Jitter frequency correspondence of the traverse
operatingamplitude
The rising time of traverse operation: it is the time
from the lowest point running to the
highestpointoftraverseoperatingfrequency.
The falling time of traverse operation: it is the time from the highestpoint runningto the
lowestpointof
traverseoperatingfrequency.
FA.12
Protection function
selection 1
Default: 1101H
Setting scope0000H1101H
FA.15
Speed tracking exciting current
percent
Default: 150.0%
Setting scope 0.0
200.0%
FA.16 Excitation time
Default: 300ms
Setting scope 10
3000ms
FA.17 Speed calculation judgment time
Default: 200ms
Setting scope 20
1000ms
FA.18 Voltage output soft start time
Default: 250ms
Setting scope 0
2000ms
6.12 FB Group Protection Function Group
Fb.00
Protection function
selection 1
Default: 1101H
Setting scope0000H1101H
Single digitOver-voltage stall protection