Specifications

Chapter6FunctionalParameterDetailVFDG7SeriesFrequencyInverterOperationManual
142
F9.05
Accumulative
conduction time hours
DefaultThis parameter is
read-only.
Setting scope
H
F9.06
Accumulative
conduction time
minutes
DefaultThis parameter is
read-only.
Setting scope
Min
6.11 FA Group Enhancement Function Group
FA.00
Jog running
frequency
Default10.00Hz Setting scope: 0.00
F0.05
FA.01
Acc time of Jog
operation
Defaultdetermine according
to type
Setting scope: 0.1
3600.0s
FA.02
Dec time of Jog
operation
Defaultdetermine according
to type
Setting scope: 0.1
3600.0s
Acc time of Jog operation: the drive needs the time from 0Hz accelerating to Maximum
outputfrequency.
Dec time of Jog operation: the drive needs the time from Maximum output frequency
deceleratingto0Hz.
FA.03 Acc time 1
Default: Determine
according to type
Setting scope: 0.1
3600.0s
FA.04 Dec time 1
Default: Determine
according to type
Setting scope: 0.1
3600.0s
The Acc/Dec time 0 during the running process of frequency invertercouldbe selected by
themultifunctiondigitalinputterminals.IfselectingthemultifunctionterminalofAcc/Dec
timeclose,thenselectAcc/Dectimeofthisgroupto1.
In the forward and reverse transient process of the frequency inverter,
set the transient