Specifications
VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
141
2:Validforpanelandcommunicationcontrolinthesametime
3:Validfortheentirecontrolmode
F9.01
Normal monitoring parameter selection
when stop
Default:1Setting scope:0~30
This parameteris used to ensure the display content of the operation panelunder normal
monitoring mode. Under normal monitoring mode, the following six parameters are
displayed through >>/SHIFT key: running frequency, setting frequency, busbar voltage,
output current, output voltage, running speed. If there is without any pressing within one
minute, it will be back to the normal monitoring mode, the keyboard will display the
parameter variable selected by F9.01. The corresponding monitoring parameter and the
corresponding
rangecouldrefertoFFgroupparameterFF.00~FF.30.
F9.02
Normal monitoring parameter selection
when running
Default:0Setting:0~30
Ifthereisothervariable‐speedgearlikereducercasinginthedrivingsystem,thisparameter
couldbechangedtomaketheshowingspeedinconformitywiththeactualsystem.
F9.03 User password
Default:0 Setting scope:0~65535
Thepasswordprotectionfunctionwillbevalidwhensettingtoanynonzeronumber,please
do remember the setting user password. When set to 00000, clear the user password set
beforeandmakethepasswordprotectionfunctioninvalid.
When the user password is set and valid, if the user password is wrong,
the user couldn’t
enterintoparametermenu,onlytoinputtherightuserpasswordcouldtheusercheckand
modifytheparameter.
Exit function code editing state, the password protection will come into effect within
1 minutes, when enter into function code editing state by pressing MODE key after the
password come into effect, 0.0.0.0.0.will be displayed, the user should input user
password rightly, otherwise, the user couldn’t enter.
Notes: please modify the user password carefully, otherwise, problem would occur
to the system.
F9.04 Reserve
Default: Setting scope: