VFDG7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
139
2Oddparity(081)forRTU
3Noparity(N82)forRTU
4Evenparity(E82)forRTU
5Oddparity(Q82)forRTU
The host PC and drive must have the same data format; otherwise, the data can not be
communicated.
F8.02 Delay for responding
Default: 5ms
Setting scope0200ms
It refers to the waiting time from drive receiving the host PC command to returning
responseframetoit.
F8.03
The fault time of
Communication overtime
Default: 0.0s
Setting scope0.0s invalid 0.1
100.0s
When this function code is set to 0.0S, communication overtime fault judgment is not
conducted. When the time is set to non 0, if the spacing interval between this
communication and next communication exceeds the communication overtime time, the
systemwillreportcommunicationfaulterror(E018).
F8.04
Communication response
handling
Default
0001H
Setting scope0000H0013H
Single digitTransmission error handling
0Alarmandcoasttostop
1Noalarmandcontinuerunning
2Noalarmandstopinstoppingmode(onlyincommunicationcontrolmode)
3Noalarmandstopinstoppingmode(inallcontrolmodes)
The drive can select to shield failure alarm and shutdown and Reserve operating in
the
abnormalcommunication.
DecadeTransmission response handling