VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
139
2:Oddparity(0,8,1)forRTU
3:Noparity(N,8,2)forRTU
4:Evenparity(E,8,2)forRTU
5:Oddparity(Q,8,2)forRTU
The host PC and drive must have the same data format; otherwise, the data can not be
communicated.
F8.02 Delay for responding 
Default: 5ms 
Setting scope:0~200ms 
It refers to the waiting time from drive receiving the host PC command to returning
responseframetoit.
F8.03 
The fault time of 
Communication overtime 
Default: 0.0s 
Setting scope:0.0s invalid 0.1~
100.0s 
When this function code is set to 0.0S, communication overtime fault judgment is not
conducted. When the time is set to non 0, if the spacing interval between this
communication and next communication exceeds the communication overtime time, the
systemwillreportcommunicationfaulterror(E018).
F8.04 
Communication response 
handling 
Default  :
0001H 
Setting scope:0000H~0013H 
Single digit:Transmission error handling 
0:Alarmandcoasttostop
1:Noalarmandcontinuerunning
2:Noalarmandstopinstoppingmode(onlyincommunicationcontrolmode)
3:Noalarmandstopinstoppingmode(inallcontrolmodes)
The drive can select to shield failure alarm and shutdown and Reserve operating in
 the
abnormalcommunication.
Decade:Transmission response handling 