Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
138
The system always detect the PID feedback value, when feedback value is bigger than
feedback disconnection detection value, the system begin to detect and time, when
duration exceeds feedback oversize detection time, the system would select to run
continuouslyorfaultaccordingtofeedbackoversizemotion.
6.9 F8 Group Communication Parameter
F8.00
Local communication
address
Default: 1
Setting scope:0: is the broadcasting address
1~247
The Local address is unique in the communication network, which is the basis to achieve
pointtopointcommunicationbetweenPCanddrive.
When the slave communication address is set to “0”, it is the broadcast communication
address,alldrivesontheMODBUScanreceivetheframe,butwillnotanswer
thePC.
F8.01
Communication
configuration
Default: 0003H
Setting scope:0000H~0055H
Single digit:Baud rate set
0:1200BPS
1:2400BPS
2:4800BPS
3:9600BPS
4:19200BPS
5:38400BPS
ThisparameterisusedtosetthedatatransmissionspeedbetweenhostPCanddrive.
☞Note: the host PC’s and drive’s baud rate must be same, otherwise, the communication
cannotbedone.Thebiggerbaudrate,the
fastercommunicatingspeedwillbe.
Decade:Data bit parity setting
0:Noparity(N,8,1)forRTU
1:Evenparity(E,8,1)forRTU