Specifications

VFDG7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
137
run frequency set F0.05
ThesystemwillalwaysdetectthePIDfeedbackvalue,whenthefeedbackvalueislessthan
the feedback disconnection detected value, the system will begin to time for detection.
Whenthedurationisoverthefeedbackdisconnectiondetectedtime,thesystemwillselect
runcontinuouslyorreportfaultaccordingtofeedback
disconnectionmotion.
F7.09 Sleep frequency
Default: 0.00Hz
Setting scopeF0.08F0.05
When the sleep frequency is set to 0, the sleep function couldn’t be started. When
dormancyfrequencyis setto 0or notusing PID,thelower limitfrequency couldbebigger
than sleep frequency, otherwise, the lower limit frequency need to be less than sleep
frequency;itrunsaccordingto
themodesetbyF0.24whenPIDfrequencyislessthanlower
limitfrequency.
F7.10 Sleep delay
Default: 120.0s
Setting scope0.03600.0s
IftheoutputfrequencyofPIadjustedvalueislessthansleepfrequency(F7.09),theduration
islargerthesleepdelaytimeofthefrequency,thedrivewillstopandintothesleepstate.
F7.11 Wakeup value
Default: 10.0%
Setting scope0.0100.0%
ThisparameterisusedtoensurethePIDfeedbackvaluewhichisusedinthewakeupstartof
thefrequencyinverter.
F7.12 Wakeup delay
Default: 30.0s
Setting scope0.03600.0s
WhenPIDfeedbackvalueislessthanthiswakeupvalueandthedurationtimeexceedsthe
wakeupdelaytime,thefrequencyinverterexitsleepstateandbegintooutputfrequency.
F7.13
PID feedback oversize detection
value
Default:
100.0%
Setting scope: 20.0
100.0%
F7.14
PID feedback oversize detection
time
Default: 3.0s
Setting scope0.03600.0s
F7.15
PID feedback oversize alarm run
fixed frequency set
Default:
0.00Hz
Setting scope0.00F0.05