Specifications
 Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
136
0:Invalid
1:Alarmandruninfixedfrequency.
FAULTindicatorlightflash,therunningfrequencyisfixedatthefrequencysetbyF7.14.
2:Faultstop
FaultE024。
F7.02 
Keyboard digital PID 
reference 
Default: 0.0% 
Setting scope:0.0%~100.0% 
ThisparameterneedtobesetinkeyboardpresetofPIDgoalsource.
F7.03 Proportional gain (KP)
Default: 5.00
Setting scope:0.00~50.00 
F7.04 Integral time (Ti) 
Default: 0.40s
Setting scope:0.01~50.00s 
Proportionalgain(Kp):determinesintensityofPIDconditioner.Thebiggertheproportional
gainofKP,thebiggerintensity.
Integral time (Ti): determines the integral speed of the PID conditioner for error between
thePIDreferenceandfeedbackvalue.
F7.05  The limit of PID control slip 
Default: 0.0% 
Setting scope:0.0~100.0%
This parameter defines the max deviation relative to close‐loop set point, PID regulator
stops operation when the feedback value is within this range. Setting this parameter
correctly is helpful to improve the system output accuracy and stability. This function is
mainlyusedinthesystemwheretherequirementoncontrol
accuracyislowandthereisno
frequentadjustment,suchastheconstantvoltagewatersupplysystem.
F7.06 
The value of feedbac
k
disconnection detected 
Default: 0.0% 
Setting scope : 0.0 ~
100.0% 
F7.07 
Feedback disconnection detected
time 
Default: 10.0s 
Setting scope : 0.0 ~
3600.0s 
F7.08 Feedback  disc onnection alarm 
Default: 25.00Hz
Setting scope : 0.00 ~