Specifications
Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
136
0:Invalid
1:Alarmandruninfixedfrequency.
FAULTindicatorlightflash,therunningfrequencyisfixedatthefrequencysetbyF7.14.
2:Faultstop
FaultE024。
F7.02
Keyboard digital PID
reference
Default: 0.0%
Setting scope:0.0%~100.0%
ThisparameterneedtobesetinkeyboardpresetofPIDgoalsource.
F7.03 Proportional gain (KP)
Default: 5.00
Setting scope:0.00~50.00
F7.04 Integral time (Ti)
Default: 0.40s
Setting scope:0.01~50.00s
Proportionalgain(Kp):determinesintensityofPIDconditioner.Thebiggertheproportional
gainofKP,thebiggerintensity.
Integral time (Ti): determines the integral speed of the PID conditioner for error between
thePIDreferenceandfeedbackvalue.
F7.05 The limit of PID control slip
Default: 0.0%
Setting scope:0.0~100.0%
This parameter defines the max deviation relative to close‐loop set point, PID regulator
stops operation when the feedback value is within this range. Setting this parameter
correctly is helpful to improve the system output accuracy and stability. This function is
mainlyusedinthesystemwheretherequirementoncontrol
accuracyislowandthereisno
frequentadjustment,suchastheconstantvoltagewatersupplysystem.
F7.06
The value of feedbac
k
disconnection detected
Default: 0.0%
Setting scope : 0.0 ~
100.0%
F7.07
Feedback disconnection detected
time
Default: 10.0s
Setting scope : 0.0 ~
3600.0s
F7.08 Feedback disc onnection alarm
Default: 25.00Hz
Setting scope : 0.00 ~