VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
133
Singledigit:cyclemodeselection
0:Stopafteroperatingfor1cycle(timingstopfunctioncouldbeachieved.thedrivestops
automatically after one cycle of operation and will start when receiving RUN command
again.
1:Holdingatthefinalvalueaftersinglecycleofoperation
Thedrivewillmaintain
theoperatingfrequencyanddirectionoflaststageaftercompleting
onecycleofoperation.
2:Cyclecontinuously(validafterstop)
The drive will start next cycle of operation automatically after completing one cycle of
operationuntilreceivingSTOPcommand,thesystemwillstop.
Decade:PLC breaking point recovering mode selection
0: Operate from first section
1:Continuefromthestagefrequencywherethedrivestops
2:Continuetooperateattherunfrequencywhenthedrivestops
Hundreds:PLC mode saving at power down
0:Notsaving
1:Saving
PLC saving at power cut refers to PLC run stage and run frequency before storage power
down.PLCstopstoragereferstothestorageofPLCrunstageandrunfrequencyaftergiving
thestopcommand.
Kbit:Stage time limit
0:S
1:Min
F6.33 PLC goal setting unit selection
Default: Setting scope:0~1
0:Percentsetting