VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
129
The corresponding relation of output is similar with FM1.
6.7 F6 Group Multi-speed and PLC Program Run
SimplePLC function isa multi‐segmentspeedgenerator, itcan enablethedrive changeits
operatingfrequencyanddirectionsautomaticallyaccordingtotheoperatingtimetosatisfy
the manufacturing requirements. This frequency inverter series could achieve 16 section
speedcontrol.AfterthesettingPLCfinishacirculating(orastage),
apulsesignalwouldbe
outputbythe multi‐functiondigitaloutputterminalor multi‐functionrelay, theduration is
500ms,itisasthefollowingfigure6‐15.
F5.25 FM2 output lower limit percent
Default:0.0% Setting scope:0.0~100.0%
F5.26
FM2 lower limit corresponding
output
Default:0.00V Setting scope:0.0~10.00V
F5.27 FM2 output upper limit percent
Default :
100.0%
Setting range:0.0~100.0%
F5.28
FM2 upper limit corresponding
output
Default :
10.00V
Setting range:0.0~10.00V
F5.29
HDO high speed pulse output
lower limit percent
Default:0.0% Setting range:0.0~100.0%
F5.30
HDO lower limit corresponding
output
Default :
0.00kHz
Setting range: 0.0 ~
50.00kHz
F5.31
HDO high speed pulse output
upper limit percent
Default :
100.0%
Setting range:0.0~100.0%
F5.32
HDO upper limit corresponding
output
Default :
50.00kHz
Setting range: 0.0 ~
50.00kHz