VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
127
voltageoutputcouldbeselectedthroughJP9andJP10jumpers.The outputrangeofHDO
ofopencollectorhighspeedpulseis0.0~50.0kHz.
Notes:TheoutputofHDOofopencollectorhighspeedpulseisonlyvalidinVFcontrolmode
(F0.014=1).
The representative corresponding variable range is as follows:
Set value Function Range
0 Running frequency 0~max output frequency
1 Setting frequency 0~max output frequency
2 Busbar voltage 0~2 times standard busbar
3 Output current 0~2 times frequency inverter rated current
4 Output voltage 0~1.5 times frequency inverter rated voltage
5 Running speed 0~3 times motor rated speed
6 Output power 0~2 times motor rated power
7 Setting torque 0~2 times frequency inverter rated current
8 Output torque 0~2 times frequency inverter rated current
9 PID setting 0.0~100.0%
10 PID feedback 0.0~100.0%
11 Analog V1 input value 0.0~10.0V
12 Analog V2 input value 0.0~10.0V/ 0~20mA
13 HDI high speed pulse
input frequency
0.0~50.00kHz
14 Retain
15 Retain