Specifications

VFDG7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
123
F5.05 Relay 4 output selection Default: 0
F5.06 Relay 5 output selection Default: 0
0Nooutput
1Frequencyinverterinservice
Whenthefrequencyinverterruns,ONsignalisoutput.
2Frequencyinverterisready
Whenfrequencyinverterisinhaltmodeandwithoutfault,ONsignalisoutput.
3Frequencyinverterisinfault
Whenfaulthappenstofrequencyinverter,ONsignalis
output.
4FrequencyleveldetectsFDToutput.
5Setfrequencyarrival
6Zerospeedinservice
Whentheoutputfrequencyis0,ONsignalisoutput.
7Upperlimitfrequencyarrival
Whenrunningfrequencyarrivesupperlimitfrequency,ONsignalisoutput.
8Lowerlimitfrequencyarrival
Whenrunningfrequency
arriveslowerlimitfrequency,ONsignalisoutput.
09:OutputisfinishedduringPLCprogramrunningstage
A500mswidthpulsesignalisoutputwhenPLCprogramrunfinishesastage.
10OutputisfinishedduringPLCprogramcirculating
A 500ms width pulse signal is output when PLC program run
finishes a circulation this
functionisinvalidifitissettocontinuouscycle.
11DCbrakinginprocess
12TorqueleveldetectsFDToutput
13Retain
14Retain
15Runinreverse
16Retain