120
currenteffectiveAcc/Dectime;
24:Selectionoftheauxiliaryfrequencysource
Whentheterminalwith functionis setto close,the auxiliaryfrequencysourceselected by
F0.03isregardedasvalidreferencefrequency.
Notes: this function is prior to the main and auxiliary frequency source switch set by
QUICK/JOG.
25:Pause
thesimplePLCprogramoperation
26:Reserve
27: Reserve
28: Stop DC braking control
29: Reserve
30: Reserve
F4.10 Filter times of the switch Default: 5
Setting scope 010
The parameter is used to set the filter time of S1~S10 terminals’ sampling. In the case of
largedisturbance,theparametershouldbeincreasedtoavoidmalfunction
F4.11 Lower limit of V1
Default0.00v Setting scope 0.00F4.13
F4.12
The reference percent
corresponding to lower limit
of V1
Default0.0%
Setting scope -100.0
100.0%
F4.13 Upper limit of V1
Default10.00V
Setting scope F4.11
10.00V
F4.14
The reference percent
corresponding to upper limit o
f
V1
Default100.0%
Setting scope -100.0
100.0%
F4.15 Filter time of input V1
Default0.10s Setting scope0.0010.00s
The above function code defines the relationship between the analog input voltage’s and