Specifications
VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
119
13:Multi‐speedterminal2
14:Multi‐speedterminal3
15:Multi‐speedterminal4
Thecombinationofthe4terminal’sdigitalstatuscanset16kindsofspeed.
Note:themulti‐speed1isthelowbit,themulti‐speed4ishighbit,whenthemulti‐speedis
not0,ithas
thehighestpriority.
16:PausePIDcontrol
ThePIDcontrolistemporaryinvalid,thedrivewillReservethecurrentoutputfrequency.
17:Pausetraverse(holdthecurrentfrequency)
ThedrivepausesandReservesthecurrentfrequency,whenthefunctionrecovers,thedrive
willtraverseoperatewiththecurrentfrequency.
18:
Traversereset(returnthecentralfrequency)
Thedrivewilloutputthecentralfrequency.
19:Acc/Decsuspension
Ensure the drive free from the external signals (except the stop signal), and Reserve the
currentoutputfrequency.
20:Torquecontrolbanned(undertorquecontrol,switchtospeedcontrolforcibly)
Thedrivewillforbidusing
torquecontrolmode,andwillswitchtothespeedcontrol.
21:TemporarilyclearthefrequencyUPorDOWNsetting
If the terminal is closed, the reference frequency via the UP/DOWN will be clear, and the
frequencywillreturntothereferencefrequencyofthereferencefrequencychannel.Ifthe
terminal
isopen,thefrequencywillreturntothereferencefrequencyofUP/DOWNsetting.
22:SimplePLCprogramsegmentreset
Thefunctionterminalclosesoncetime,thePLCoperationwillberesetandbeginfromthe
firststage.
23:Acc/Dectimeselection
Whentheterminalwithfunctionissettoclose,select
Acc/Dectime1(FA.03、FA.04)asthe
current effective Acc/Dec time; otherwise, select Acc/Dec time 0(F0.10、F0.11)as the