Specifications
Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
118
It is the frequency of Jog operating. The Acc/Dec time of Jog operation can be referred to
thedescriptionoffunctioncodesFA.00~FA.02.
6:Coasttostop(onlyvalidwhenterminalcontrolF0.01=1)
The stop process will not be controlled by drive. It is the common method of great
load
inertiaandnorequirementofstoptime.
7:Faultreset
ThefunctionissameastheSTOP/RESETkey.ThefunctioncanachieveRemoteFaultReset.
8:Externalfaultinput
Whenthedrivereceivesthesignalofexternalfault,thedrivewillalarmandstop.
9:Frequencysettingincrease(UP)
10:
Frequencysettingdecrease(DOWN)
11:Frequencyincreaseanddecrease(UP/DOWN)settingclearing
When the reference frequency is set by external terminals, the function will be used to
adjust the frequency increase instruction and decrease instruction. When the source of
referencefrequency isthedigital setting, the functioncanbe used
to adjust the reference
frequencyforup/down,theterminalspeedregulationisasshowninfig,6‐10.
Figure6‐10Illustrationofterminalspeedregulation
The terminals can be used to clear the reference frequency by UP/DOWN, and make the
frequencyreturntothereferencefrequencybythechannelofthereferencefrequency.
12:Multi‐speedterminal1