Specifications
VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
117
2:Upperlimitoffrequency(F0.06)issetbyAnalogV2
3:Upperlimitoffrequency(F0.06)issetbyRemotecommunication
Notes 1:When it is set to 0-3,100% correspond to the max frequency F0.05. 
6.5 F4 Group Input Signal Group 
F4.00  S1 Terminal function selection Default: 1 
Setting scope: 0~30 
F4.01  S2 Terminal function selection Default: 2 
F4.02  S3 Terminal function selection Default: 7 
F4.03  S4 Terminal function selection
Default: 0 
F4.04  S5 Terminal function selection
F4.05  S6 Terminal function selection
F4.06  S7 Terminal function selection
F4.07  S8 Terminal function selection
F4.08  S9 Terminal function selection
F4.09  S10 Terminal function selection
0:Nofunction
Even if there are input signals, the drive will not run. The unused terminals can be set no
functioninordertoavoidmalfunction.
1:Forward
2:Reverse
Theexternalterminalscontrolthedriveoperatingdirection.
3:3‐wireoperationcontrol
The terminal is used to set the
 drive’s operating mode of 3‐wire operation control, please
refertothedescriptionof3‐wireoperationcontrolfunctioncodeF0.13.
4:Jogforward
5:Jogreverse