Specifications
VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
113
F3.05 inductance o
f
stator and rotor
model 6553.5mH
F3.06
Exciting
inductance o
f
stator and rotor
Default: Dependent on drive’s
model
Setting scope:0.1~
6553.5mH
F3.07
Current without
load
Default: Dependent on drive’s
model
Setting scope: 0.1~
655.3.5A
Whentheauto‐learningofmotor’sparametersnormallyends,thesettingvaluefromF3.03
to F3.07 will automatically update. These parameters are the benchmarks of
high‐performancevectorcontrol,anddirectlyaffectthecontrolperformance.
☞Note:Usersdonotarbitrarilychangethegroupofparameters.
F3.08 Parameter auto-learning Default: 0
Setting scope:0~2
0:Nooperation
Theauto‐learningisbanned.
1:Dynamicauto‐learning
Before starting auto‐learning, please ensure the motor and load being disconnected,
Reservethemotorno‐loadandconfirmthemotorinthestandstillstate.
Values on the motor’s nameplate (F3.01~F3.02) must be input correctly before starting
auto
‐learning,otherwise,theauto‐learnedparametersarenotcorrect.
The size of Acc/Dec time (F0.10~F0.11) should be properly set according the size of the
motor’s inertia before starting auto‐learning, otherwise, the over‐current fault may be
causedduringauto‐learning.
F3.08 is set to 1, then press ENTER key, the system begins auto‐learning. Now, the LED
flashing displays‐TUN‐, press RUN key, the LED displays TUN‐0, after the motor running,
TUN‐1 isdisplayed andthelightRUNflashes.Whentheauto‐learningends, the‐END‐will