Specifications
Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
112
Whensuppressoscillation,theparametercanbeusedtolimittheboostvalueofbigvoltage.
F2.15
Boundary frequency between high and
low frequency of suppress oscillation
Default :
12.50Hz
Setting scope:0.00~
F0.05
F2.15istheboundaryofthefunctioncodesF2.12andF2.13.
6.4 F3 Group Vector and Torque Control Parameter
F3.00
Motor rated
power
Default: Dependent on drive’s
model
Setting scope:0.4~
900.0KW
F3.01
Motor rated
current
Default: Dependent on drive’s
model
Setting scope:0.4~
1000.0A
F3.02
Motor rated speed
Default: Dependent on drive’s
model
Setting scope:0~
36000RPM
☞Note:pleasesetwithreferencetothevaluesonthemotor’snameplate.Excellentcontrol
performanceofvectorcontrolshouldhaveaccuratemotor’sparameters.
The drive has auto‐learning function of motor’s parameters. Only correctly setting the
parametersofthemotor’snameplatecanensuretheaccuracyofauto‐learning.Inorder
to
ensurethecontrolperformance,pleaseconfigurethemotoraccordingtostandardadaptive
motorofthefrequencyinverter.Ifthemotor’spowerandthatofstandardadaptivemotor
haveawidegap,thecontrolperformancewillsignificantlydecrease.
☞Note: the motor parameter from F3.01 to F3.07 could be initialized by
resetting motor
ratedpowerF3.00.
F3.03
Resistance o
f
stator
Default: Dependent on drive’s
model
Setting scope:0.001~
65.535Ω
F3.04
Resistance o
f
rotor
Default: Dependent on drive’s
model
Setting scope:0.001~
65.535Ω
Leakage Default: Dependent on drive’s
Setting scope:0.1~