VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
111
F2.09 Custom V/F percentage Default: 100.0%
Setting scope:50.0~100.0%
F2.10 V/F slip compensation gain Default: 0.0%
Setting scope:0.0~200.0%
SettingthisparametercouldcompensatethemotorspeedchangecausedbytheloadinV/F
control, which can improve the hardness of motor mechanical characteristics, this value is
correspondingtothemotor’sratedslipfrequency.
F2.11 Suppress oscillation enabled Default: 1
Setting scope:0~1
0:Suppressoscillationvalid
1:Suppressoscillationinvalid
The function code of suppression oscillation is for V/F control, the common motor with
no‐load or light‐load often has current oscillation to leadthe motor’s abnormal operation,
theseriouscan cause drive over current.When the F2.11 is selected to 0,
the suppressing
oscillation function is enabled, the drive will suppress the motor’s occurring oscillation
accordingtotheparametersoffunctionsF2.12~F2.15.
F2.12
Suppress oscillation low-frequency
threshold
Default:5 Setting scope:0~500
F2.13
Suppress oscillation low-frequency
threshold
Default:100 Setting scope:0~500
Whenmostofmotorsruninsomefrequencyband,thecurrentoscillationwilleasilyoccur,
lightcaseis thatthemotor cannotstable operate,theserious situationwillleadthedrive
over‐current.
When F2.11 is set to 0, suppress oscillation is valid. When F2.12 and F2.13 have small
reference
values, the effect of the suppress oscillation is evidence, the addition of the
currentisevidence;ifthesettingsislarge,theeffectofsuppressoscillationisweak.
F2.14
Amplitude limit of suppress
oscillation
Default: 5000
Setting scope:0~10000