Specifications
 Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
110
F2.04 
 VF point 1 voltage V1  Default: 20.0% 
Setting scope:0.1~F2.06 
F2.05 
 VF point 2 frequency
F2 
Default: 50.0% 
Setting scope:F2.03~F2.07 
F2.06 
 VF Point 2 Voltage V2 Default: 50.0% 
Setting scope:F2.04~F2.08 
F2.07 
 VF point 3 frequency
F3 
Default: 70.0% 
Setting scope:F2.05~100.0% 
(motor rated
frequency) 
F2.08 
 VF point 3 voltage V3  Default: 70.0% 
Setting scope:F2.06~100.0% 
(motor rated
voltage) 
TheabovesixparametersF2.03~F2.08definemultipointV/Fcurve,asshowninfigure6‐9.
ThesetvalueofV/Fcurveisusuallysetaccordingtomotor’sloadcharacteristics.
Notes:V1<V2<V3,F1<F2<F3.Ifthelowfrequencyvoltageissettoohigh,itwouldcause
overheatof
themotorandevenburnedandthefrequencyinvertermaybebeovercurrent
andstallorovercurrentprotection.
Figure 6-9 Illustration of V/F curve setting 