VFD‐G7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
109
F2.01 Torque boost
Default: 0.0%
Setting scope:0.0%:automatic torque boost
0.1~30.0%
F2.02
Cut-off
frequency o
f
torque Boost
Default: 20.0%
Setting scope:0.0~50.0%(motor rated
frequency)
Torque boost is mainly used in below the cut‐off frequency (F2.02), after boost, the V/F
curveafterboostisshowninfig.6‐8,thetorqueboostcanimprovetheV/Flowfrequency’s
torquecharacteristics.
Selectthevalueoftorqueaccordingthesizeofloads.Thebigloadscanselect
abiggerboost,
butthetorqueboostcannotbesettoobig.Ifthetorqueboostistoolarge,motorwillrun
with over excitation, the output current will increase, the motor will be easy to overheat,
thedrive'soutputcurrentwillbebig,theefficiencywillreduce.
When
thetorqueboostissetto0.0%,theinverterisautotorqueboost.
Cut‐offpointoftorque boost: thelinear V/F curve is valid,under this frequencypoint, the
torqueboostisvalid,overthepoint;thetorqueboostisinvalid.
Figure 6-8 Illustration of torque boost
F2.03
VF point 1 frequency
F1
Default: 20.0%
Setting scope:0.1~F2.05