Specifications
Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
108
when trip-free 50.00Hz/s
When the frequency scale of decrease after power cut immediately is set to 0, frequency
dropfunctionafterpowercutimmediatelyisinvalid.
Frequency point drop after power cut immediately: after the power grid power down,
busbarvoltageisdowntoFrequencypointdropafterpowercutimmediately,thefrequency
inverter
begintolow therunningfrequencyaccordingto frequencyscaleofdecreaseafter
powercutimmediatelytoReservethemotoringeneratingstateandtomaintainthebusbar
voltage by the feedback electric energy, which could guarantee the normal running of
frequencyinverteruntilthenextpoweron.
Adjusting these
two parameters properly could avoid the production halt caused by
frequencyinverterprotectionduringpowergridswitch.
6.3 F2 VF Control Parameter Group
F2.00 V/F curve setting Default: 0
Setting scope:0~3
ThisgroupfunctioncodeisvalidtoV/Fcontrol(F0.14=1),andisinvalidtovectorcontrol.
0: Linear V/F curve, it is applied to constant torque load, the output voltage is linear with
outputfrequency.
1:2.0timespowerdroptorqueV/Fcurve,seethecurveinfigure6‐7;
2:
CustomV/Fpercentage,itcanrealizemanualenergysavingcontrolbyadjustingF2.09;
3:MultipointVFcurve,itcansettheneededV/FcurvethroughfunctioncodeF2.03~F2.08.
Figure 6-7 Illustration of V/F curve