Specifications
 Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
106
F1.05 
Stop function
selection 
Default: 0010H
Setting scope:0000H~0021H 
Unitdigit:stopmodeselection
0:Dectostop
Afterreceivingthestoppingcommand,thedrivereducesitsoutputfrequencyaccordingto
theDecmodeandthedefinedDectime,andstopswhenthefrequencydecreasesto0.
1:Coasttostop
After receiving the stopping command, the drive stops outputting
 power immediately and
themotorstopsundertheeffectsofmechanicalinertia.
Decade: Stop DC Braking Enabled   
0: Disabled, DC braking is not conducted when deceleration and stop; 
1: The start frequency of DC braking is decided by F1.06 
In the process of deceleration and stop, when the output frequency is less than the 
frequency set by F1.06, braking is conducted according to the parameter defined 
according to F1.07~F1.09. 
2: The start frequency of DC braking is decided by external terminal 
In the process of deceleration and stop, when one multi-function input terminal is set to 
28 and the corresponding terminal input signal is valid, braking is conducted according to 
the parameter defined according to F1.07~F1.09 at the current frequency. 
F1.06 
Stop braking start 
frequency 
Default: 0.00Hz
Setting scope:0.00Hz~F0.05 
 F1.07 Stop braking waiting time Default: 0.0s 
Setting scope:0.0~50.0s 
 F1.08 Stop DC braking current  Default: 0.0% 
Setting scope:0.0~150.0% 
 F1.09 Stop DC braking time  Default: 0.0s 
Setting scope:0.0~50.0s 
Stop braking start frequency: in the process of deceleration and stop, when output
frequencyreachesthisfrequency,itbeginstoenterintostopbrakingwaiting;
Stopbrakingwaitingtime:duringtheperiodofstopbrakingwaiting,thefrequencyinverter