Specifications

Chapter6FunctionalParameterDetailVFDG7SeriesFrequencyInverterOperationManual
106
F1.05
Stop function
selection
Default: 0010H
Setting scope0000H0021H
Unitdigit:stopmodeselection
0:Dectostop
Afterreceivingthestoppingcommand,thedrivereducesitsoutputfrequencyaccordingto
theDecmodeandthedefinedDectime,andstopswhenthefrequencydecreasesto0.
1:Coasttostop
After receiving the stopping command, the drive stops outputting
power immediately and
themotorstopsundertheeffectsofmechanicalinertia.
Decade: Stop DC Braking Enabled
0: Disabled, DC braking is not conducted when deceleration and stop;
1: The start frequency of DC braking is decided by F1.06
In the process of deceleration and stop, when the output frequency is less than the
frequency set by F1.06, braking is conducted according to the parameter defined
according to F1.07~F1.09.
2: The start frequency of DC braking is decided by external terminal
In the process of deceleration and stop, when one multi-function input terminal is set to
28 and the corresponding terminal input signal is valid, braking is conducted according to
the parameter defined according to F1.07~F1.09 at the current frequency.
F1.06
Stop braking start
frequency
Default: 0.00Hz
Setting scope0.00HzF0.05
F1.07 Stop braking waiting time Default: 0.0s
Setting scope0.050.0s
F1.08 Stop DC braking current Default: 0.0%
Setting scope0.0150.0%
F1.09 Stop DC braking time Default: 0.0s
Setting scope0.050.0s
Stop braking start frequency: in the process of deceleration and stop, when output
frequencyreachesthisfrequency,itbeginstoenterintostopbrakingwaiting;
Stopbrakingwaitingtime:duringtheperiodofstopbrakingwaiting,thefrequencyinverter