VFDG7 Series Frequency Inverter Operation ManualChapter 6 Functional Parameter Detail
105
afterthefrequencyinverterpowerdown.
1:Restartafterpowerdownisallowed
Itindicatesthatthefrequencyinverterwouldbebacktotherunningstatebeforepowercut
automaticallywhen thefrequencyinverter poweronafter thepowercut. Thatis, if itis in
runningstatebeforepowercut,
afterthepowerisonagain,therestartwaitingtimesetby
F1.10willbedelayedanditwillstarttorunautomatically,ifitisinstopstatebeforepower
cut, the frequency inverter won’t start automatically after power on. This function is only
validtokeyboardcontrol.
Notes:
the user should select allowed restart function cautiously, otherwise, serious
consequencewouldbecaused.

F1.01 Directly start frequency
Defaul0.00Hz Setting scope0.0010.00Hz
F1.02 Start frequency holding time
Default0.0s Setting scope0.050.0s
Setting the appropriate starting frequency can increase the starting torque. Within start
frequency holding time (F1.02), the frequency inverter output frequency is the start
frequency, and then run from the start frequency to the target frequency, if the target
frequencyislessthanstartfrequency(F1.01),thefrequencyinverterwillnot
runandwillbe
inthestandbystate.Startingfrequency(F1.01)isnotrestrictedbythelowerlimitfrequency.
Intheprocessofforwardandreverseswitch,thestartfrequency(F1.01)willnotfunction.

F1.03
Start DC braking
current
Default: 0.0%
Setting scope0.0150.0
F1.04 Start DC braking time Default: 0.0s
Setting scope0.050.0s
Whenthedrivestarts,firsttoDCbrakingwiththepresetstartDCbrakingcurrent,afterthe
presetstartDCbrakingtime,thedrivewillbegintoacceleratedrun.TheDCbrakingisinvalid
ifthesettingDCbrakingtimeis0.
DCbrakingcurrentisgreater,thebrakingforceis
greater.StartingtheDCbrakingcurrentis
apercentagevaluerelativetothedrive’sratedcurrent.