Specifications

Chapter6FunctionalParameterDetailVFDG7SeriesFrequencyInverterOperationManual
104
0:Directonstarting
Startfromthepresetstartingfrequency(F1.01).
1:DCbrakingfirst,thenstart
DCbrakingfirst,thenstartfromstartingfrequency.Itissuitableforsmallinertialoadwhich
mayreverseatthestart.
2:Speedtracking,thenstart
Firstly,thefrequencyinvertercalculatesthemotor’srunning
speedanddirection,andmove
tosettingfrequencyfromtrackingspeedtoachievesmoothnoimpactstarttotherotating
motor. The method is applicable the large inertia load to restart after the drive stops
instantly.
Notes:themachinetypebelow5.5kwiswithoutspeedtrackingfunction.
Decade:Reserve
Hundred:Poweronterminalrunningprotectionselection
Whentherunninginstructionchannelisterminalcontrol,intheprocessofpoweronofthe
frequency inverter, the system will detect the running terminal’s state automatically, and
conductcorrespondingcontrolaccordingtothemultifunctioninputterminalfunction.
0:terminalrunningcommandis
invalidwhenpoweron
Even though the running command terminal is detected valid in the process of power on,
the frequency inverter will not run, the system will in the running protection state, until
disconnecting the running command terminal, then to close the terminal, the frequency
inverterwillrun.
1:
Terminalrunningcommandisvalidwhenpoweron
If the running command terminal is detected valid in the process of power on, after the
initialization,thesystem willstart therunningoffrequencyinverter automatically.Thisset
couldachievetherestartafterpowercutfunctionunderthecontrolofterminal.
Notes:
thisfunctionmaycauseseriousconsequence,theusershouldselectcautiously.
Kbit:restartafterpowercutfunctionunderthekeyboardcontrol
0:Restartbanned
Itindicatesthatthefrequencyinverterwon’tstartautomaticallywhenpowerononceagain