Specifications
Chapter6FunctionalParameterDetailVFD‐G7SeriesFrequencyInverterOperationManual
104
0:Direct‐onstarting
Startfromthepresetstartingfrequency(F1.01).
1:DCbrakingfirst,thenstart
DCbrakingfirst,thenstartfromstartingfrequency.Itissuitableforsmallinertialoadwhich
mayreverseatthestart.
2:Speedtracking,thenstart
Firstly,thefrequencyinvertercalculatesthemotor’srunning
speedanddirection,andmove
tosettingfrequencyfromtrackingspeedtoachievesmoothno‐impactstarttotherotating
motor. The method is applicable the large inertia load to re‐start after the drive stops
instantly.
Notes:themachinetypebelow5.5kwiswithoutspeedtrackingfunction.
Decade:Reserve
Hundred:Poweronterminalrunningprotectionselection
Whentherunninginstructionchannelisterminalcontrol,intheprocessofpoweronofthe
frequency inverter, the system will detect the running terminal’s state automatically, and
conductcorrespondingcontrolaccordingtothemulti‐functioninputterminalfunction.
0:terminalrunningcommandis
invalidwhenpoweron
Even though the running command terminal is detected valid in the process of power on,
the frequency inverter will not run, the system will in the running protection state, until
disconnecting the running command terminal, then to close the terminal, the frequency
inverterwillrun.
1:
Terminalrunningcommandisvalidwhenpoweron
If the running command terminal is detected valid in the process of power on, after the
initialization,thesystem willstart therunningoffrequencyinverter automatically.Thisset
couldachievetherestartafterpowercutfunctionunderthecontrolofterminal.
Notes:
thisfunctionmaycauseseriousconsequence,theusershouldselectcautiously.
Kbit:restartafterpowercutfunctionunderthekeyboardcontrol
0:Restartbanned
Itindicatesthatthefrequencyinverterwon’tstartautomaticallywhenpowerononceagain